BE THE TOP LEADER OF CABLE
Type MHF cable could meet the following standard requirements
Conductor Size (AWG or kcmil) |
Phase conductor diameter | Neutral conductor diameter | Earth conductor diameter | Nominal Diameter | Approx. Weight | Allowable Ampacities | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Inch | mm | Inch | mm | mils | mm | Kg/Km | LBS/1000FT | Kg/Km | LBS/1000FT | 90℃ | ||
2-2-4-6 | 0.383 | 9.74 | 0.329 | 8.36 | 0.286 | 7.26 | 835 | 21.2 | 429 | 288 | 100 | |
2-2-2-4 | 0.383 | 9.74 | 0.383 | 9.74 | 0.329 | 8.36 | 894 | 22.7 | 497 | 333 | 100 | |
2/0-2/0-1-4 | 0.535 | 13.6 | 0.457 | 11.6 | 0.329 | 8.36 | 1122 | 28.5 | 796 | 535 | 150 | |
2/0-2/0-2/0-1 | 0.535 | 13.6 | 0.535 | 13.6 | 0.457 | 11.6 | 1248 | 31.7 | 963 | 647 | 150 | |
4/0-4/0-2/0-4 | 0.630 | 16.0 | 0.535 | 13.6 | 0.329 | 8.36 | 1283 | 32.6 | 123 | 754 | 200 | |
4/0-4/0-4/0-2/0 | 0.630 | 16.0 | 0.630 | 16.0 | 0.535 | 13.6 | 1469 | 37.3 | 1413 | 949 | 200 |